Honeywell Single-Function Aquastat Control - L4006H1004
- Strap-on mounting - Manual Reset Differential - 1 1/2 Inch Installation Depth
Product ID • 4006H1004001
Overview
Honeywell Single-Function Aquastat Control - Strap-on mounting - Manual Reset Differential - 1 1/2 Inch Insulation Dept - L4006H1004.
Honeywell Aquastat Controls immersion type controls for limiting or regulating temperatures of liquids in boilers or hot water tanks.
Technical Specs
Honeywell Aquastat Control L4006H1004 Techs and Specs
- Totally enclosed Micro Switch snap-acting switches operates on temperature rise to setpoint
- Visible control point scale & external adjustment screw permit easy setting
- Vertical or horizontal insertion of the sensing element
- Well immersion of the sensing element
- Temperature Ratings (operating range) 100 to 240 Degrees F
- Electric Ratings (full load) 5.1 amps at 240Vac, 8.0 amps at 120Vac
- Electric Ratings (locked rotor) 30.6 amps at 240Vac, 48.0 amps at 120Vac
- Spud Size: 1/2 Inches
- Bulb Size: 3/8 Inches X 2 7/8 Inches copper
- Differential: manual reset
- Insulation depth: 1 1/2 Inches
- Maximum pressure rating Capillary Bulb (direct immersion) = 200psi (1379kpa)
- Immersion Well = 255psi (1758kpa)
- Strap-on mounting on well mount
- Single-Function
- High limit, manual reset application
- Case dimensions 5 5/8 Inches high X 2 Inches wide X 2 1/8 Inches deep
- Includes heat-conductive compound and bracket for strap-on mounting
- Stop factory set at 240 Degrees F
- Approvals = Underwriters Laboratories, Inc.: UL component recognized - File No. MP466, Vol. 6, Sec. 1, Guide No. MBPR2
- Approvals = Canadian Standards Association: CSA certified, File No. LR95329-1
- Approvals = American Gas Association IAS, AGA Certified
Info & Links