Smith Environmental Hydronic Baseboards (The Heating Edge) Tech and Specs
|
Smith Heating Edge - HE2 Hot Water Performance Ratings
(BTU's Per Linear Foot)
|
Type
|
Flow Rate (GPM)
|
90°
|
100°
|
110°
|
120°
|
130°
|
140°
|
150°
|
160°
|
170°
|
180°
|
190°
|
200°
|
210°
|
|
Two Supplies Parallel
|
1
|
130
|
205
|
290
|
385
|
460
|
546
|
637
|
718
|
813
|
911
|
1009
|
1113
|
1215
|
|
4
|
155
|
248
|
345
|
448
|
550
|
651
|
755
|
850
|
950
|
1040
|
1143
|
1249
|
1352
|
|
Top Supply Bottom Return
|
1
|
105
|
169
|
235
|
305
|
370
|
423
|
498
|
570
|
655
|
745
|
836
|
924
|
1016
|
|
4
|
147
|
206
|
295
|
386
|
470
|
552
|
640
|
736
|
810
|
883
|
957
|
1034
|
1110
|
|
Bottom Supply - Top Return
|
1
|
103
|
166
|
230
|
299
|
363
|
415
|
488
|
559
|
642
|
730
|
819
|
906
|
996
|
|
4
|
140
|
212
|
283
|
350
|
435
|
524
|
623
|
722
|
792
|
865
|
937
|
1013
|
1093
|
|
Bottom Supply - No Return
|
1
|
75
|
127
|
169
|
208
|
260
|
311
|
362
|
408
|
470
|
524
|
576
|
629
|
685
|
|
4
|
85
|
140
|
203
|
265
|
334
|
410
|
472
|
536
|
599
|
662
|
723
|
788
|
850
|
Performance Notes: All ratings include a 15% heating effect factor. Materials of construction include all aluminum "patented" fins at 47.3 per LF, mechanically bonded to two 3/4" (075)
type L copper tubes ("Coil Block") covered by a 20 gauge perforated, painted cover all mounted to a backplate. EAT = 65° F.
|
|