Myson LST Hydronic Radiators
Low Surface Temperature Panel Hydronic Radiators
Please Note: All Myson LST Radiators are special order,
non-returnable and take 12 weeks for availability.
|
Myson LST Radiators are intended for use in space heating applications where a low surface
temperature is required (less than 109°F with inlet water at 180°F) or is desirable
for other reasons. Typical applications are hospitals, clinics, retirement homes, nurseries,
public buildings (e.g. schools, libraries, sports halls, etc) and private housing.
Description
The LST Hydronic Radiators consist of an efficient internal heat emitter in an attractive and robust
.047" (18 gauge) steel enclosure. The enclosure is designed to give protection against
high surface temperatures and also provides for concealment and security of pipework and valves.
A simple unique locking arrangement prevents unauthorized removal but gives ready and convenient
access for venting and cleaning, decorating, etc.
Surface Temperatures
Surface temperatures are below 109°F with water inlet temperature up to 180°F.
Range
The Myson LST Radiator is available in fifty-six sizes comprising four heights 22", 26",
34" and 38", and up to eight lengths from 32" to 78". Two types are
available, Super and Super Plus.
Connections
LST Myson Radiators are fitted with 1/2" BSP threaded connections.
Accessories
Concealed wall brackets, air vent, and plug are supplied with every radiator. A fitting
instruction leaflet is also included.
Pressures
Every Myson LST Hydronic Radiator is tested to a pressure of 152.5 psi and is suitable for a working
pressure of 117.1 psi.
Installation
Myson LST Radiators are for use on indirect systems only, with a maximum working temperature
of 180°F. We do not recommend the use of single feed indirect cylinders, as the possibility
of aeration due to water interchange may lead to corrosion. When installing the unit, allow for
any floor covering. For example, allow an additional 3/16" above any floor that is likely
to become wet when cleaning.
The installation work must be done in accordance with recognized good practice and precautions
taken to avoid contamination which could lead to corrosion. If a corrosion inhibitor or other
water treatment is to be used, the Manufacturer’s Instructions must be strictly followed.
Cleaning and Maintenance
Myson LST Radiators have been designed and constructed to enable venting, cleaning and maintenance
to be carried out easily without disturbance to plumbing. The casing and top grill are rounded
to prevent items from being stacked on top and reducing heat output. A simple screw prevents
unauthorized removal of the casing but gives easy access for cleaning.
Packaging
Each LST Radiator Space Heater is individually packed in a single protective cardboard carton which
displays the unique model identification code. Concealed wall brackets are a standard feature of
all models and the single piece case makes fitting easy. The Myson LST is delivered as a complete
unit from stock, but the radiator can be fitted separately in order to avoid damage to the casing
prior to installing.
Approval and Certification
All Myson LST Radiators are manufactured and tested to BS EN 442. Every radiator carries the BS
Kitemark which certifies independent approval of heat output and verifies production under a
quality system to BS EN ISO 9002.
|
|