Takagi T-K2 Water Heater - Installation Info
For more detailed information - please download a T-K2 installation manual (link at the bottom of this page) Return to T-K2 Main Page |
|||||||||||||||||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||||||||||
If the T-K2 is installed in an area smaller than indicated above, then the installer must make special provisions for combustion air in the form of two openings, each one within 12" of the top and 12" of the bottom of the space, having a total free area of 1 square inch per 1,000 Btu/hr of rated input if the air is taken from inside the house (two 13" x 13" openings). This requirement reduces to 1 square inch per 4,000 Btu/hr if the air is taken from the outside (two 6.5" x 6.5" openings). Note: This calculation assumes normal rates of "infiltration" of outside air. A super-insulated, super-tight space/building may require outside air for the T-K2 even though the volume/area of the space meets this application. Caution: In addition to the above, the T-K2 must be properly vented to ensure safe and efficient operation.
Please Note: Hot Water Heater Temperatures over 125°F can cause severe burns instantly or death from scalding. Children, disabled and elderly are at the highest risk of being scaled. Feel water temperature before bathing or showering. |
|||||||||||||||||||||||||||||||||||||||||||
|
For more information download a Takagi T-K2 installation manual in pdf format. Also see all water heater manuals from this link Return to T-K2 Main Page |
|||||||||||||||||||||||||||||||||||||||||||