Takagi T-K2 Water Heater - Installation Info
For more detailed information - please download a T-K2 installation manual (link at the bottom of this page)


Return to T-K2 Main Page


  • Technical Specs of the T-K2
Power Input Natural Gas — 20,000-185,000 BTU
LP Gas — 19,000-175,000 BTU
Water Pressure Minimum — 15 PSI
Maximum — 150 PSI
Gas Connection 3/4" Male NPT
Water Connection 3/4" Male NPT
Natural Gas Pressure Minimum — 5" WC
Maximum — 10.5" WC
LP Gas Pressure Minimum —11" WC
Maximum — 14" WC
Electrical Supply 120 Volts / 0.8 Amps
Minimum Flow to Activate 3/4 gallons per minute
Flow Rates
(50 degree Input Water Assumed)
90°F rise / 3.4 gallons per minute
80°F rise / 3.9 gallons per minute
70°F rise / 4.4 gallons per minute
60°F rise / 5.2 gallons per minute
55°F rise / 5.8 gallons per minute
50°F rise / 6.2 gallons per minute
Head Loss
when used for heating applications
39 1/4 at 6.9 gpm
Dimensions
(H x W x D)
24 inches by 18 inches by 9 inches
Out Water Temperature Factory preset at 120 degrees - can be set to 105, 112, 120 or 180 degrees with an internal dipswitch.
Optional Temperature Remote control will allow range from 95 degrees to 180 degrees.
Vent Size Indoor Installation 4" - Sealed Stainless Steel Piping
Optional Accessories Wall Hanging Kit: TK-WB01
Vent Terminator and Backflow Preventer: FXHOOD
Backflow Preventer: TK-TV03
Temperature Remote Controller


  • Required clearances for OUTDOOR INSTALLATION
Takagi T-K2 OUTDOOR INSTALLATION
TOP 36"
FRONT 24" (maintenance space)
BACK 1"
PIPING SIDE 6"
NON PIPING SIDE 2"
GROUND 3" off ground on non-combustible base


  • Required clearances for INDOOR INSTALLATION
Takagi T-K2 INDOOR INSTALLATION
TOP 12"
FRONT 4" (24" suggested for maintenance space only)
BACK 1"
PIPING SIDE 6"
NON PIPING SIDE 2"
FLOOR Non-combustible base


  • Gas & Venting for the Takagi T-K2 Gas Water Heater
It is very important to have the proper size gas line - see the T-K2 manual for more detail of pipe size or contact your local gas company or contractor.

Gas 5/8" 3/4" 7/8" 1"
Liquid Propane Not Recommended 35 feet 70 feet  
Natural Gas   25 feet   80 feet
Venting Min. Diameter Max. Vertical or Horizontal run Max. number of elbows Rule
  4 inches 35 feet 3 Deduct 5ft. for each elbow from max. vent length


  • Dimensions of the Takagi T-K2
Height Width Depth Weight
24.5" 16.5" 8.3" 65 lbs.(shipping weight)


  • Combustion Air Required (Indoor Installations) Takagi T-K2
In order to ensure an adequate supply of combustion air, the National Fuel Gas Code requires that any conventional vented gas appliance be installed in a room with a minimum volume of 50 cubic feet per 1,000 Btu/hr rated input. The following is the minimum size of the open space in which the T-K2 may be installed in compliance with this requirement:

Model Volume Area with an 8' ceiling
T-K2 9,250 cubic feet 1,156 square feet

If the T-K2 is installed in an area smaller than indicated above, then the installer must make special provisions for combustion air in the form of two openings, each one within 12" of the top and 12" of the bottom of the space, having a total free area of 1 square inch per 1,000 Btu/hr of rated input if the air is taken from inside the house (two 13" x 13" openings). This requirement reduces to 1 square inch per 4,000 Btu/hr if the air is taken from the outside (two 6.5" x 6.5" openings).

Note: This calculation assumes normal rates of "infiltration" of outside air. A super-insulated, super-tight space/building may require outside air for the T-K2 even though the volume/area of the space meets this application.

Caution: In addition to the above, the T-K2 must be properly vented to ensure safe and efficient operation.



  • Output Temperature Ratings of the Takagi T-K2
The T-K2 is factory preset at 120°. You can change the output temperature with the internal dipswitches to 105°, 112°, 120° or 180°. If you want to use any other temperatures than this - you can purchase the optional Remote Control Temperature that will allow the T-K2 to have output temperatures from 95° to 180°.

Please Note: Hot Water Heater Temperatures over 125°F can cause severe burns instantly or death from scalding. Children, disabled and elderly are at the highest risk of being scaled. Feel water temperature before bathing or showering.