Smith Environmental Products Hydronic Baseboards Tech and Specs
|
Heating Edge - HE2 Hot Water Performance Ratings
(BTU's Per Linear Foot)
|
Type
|
Flow Rate (GPM)
|
90°
|
100°
|
110°
|
120°
|
130°
|
140°
|
150°
|
160°
|
170°
|
180°
|
190°
|
200°
|
210°
|
|
Two Supplies Parallel
|
1
|
313
|
364
|
462
|
612
|
665
|
737
|
811
|
884
|
960
|
1041
|
1106
|
1193
|
1297
|
|
4
|
390
|
450
|
535
|
701
|
762
|
832
|
915
|
998
|
1084
|
1175
|
1248
|
1346
|
1463
|
|
Top Supply Bottom Return
|
1
|
289
|
338
|
417
|
589
|
640
|
693
|
753
|
814
|
877
|
913
|
932
|
1001
|
1089
|
|
4
|
380
|
411
|
514
|
670
|
728
|
781
|
849
|
919
|
992
|
1031
|
1051
|
1129
|
1223
|
|
Bottom Supply - Top Return
|
1
|
172
|
201
|
265
|
419
|
455
|
516
|
572
|
628
|
685
|
765
|
835
|
903
|
983
|
|
4
|
228
|
326
|
355
|
485
|
527
|
586
|
649
|
712
|
777
|
863
|
947
|
1017
|
1108
|
|
Bottom Supply - No Return
|
1
|
176
|
211
|
277
|
434
|
472
|
530
|
586
|
642
|
715
|
775
|
840
|
907
|
988
|
|
4
|
226
|
286
|
347
|
500
|
544
|
600
|
663
|
724
|
792
|
875
|
948
|
1025
|
1062
|
|
Top Supply - No Return
|
1
|
115
|
145
|
193
|
308
|
335
|
392
|
445
|
497
|
547
|
648
|
751
|
818
|
896
|
|
4
|
141
|
180
|
228
|
358
|
389
|
446
|
506
|
567
|
620
|
733
|
847
|
924
|
1012
|
Performance Notes: All ratings include a 15% heating effect factor. Materials of construction include all aluminum "patented" fins at 47.3 per LF, mechanically bonded to two 3/4" (075)
type L copper tubes ("Coil Block") covered by a 20 gauge perforated, painted cover all mounted to a backplate. EAT = 65° F.
|
|